Status 3-20 Way Alarm Panel

Specifications

Power Supply - 230/110V AC and/or 24V DC
Power consumption max - 15 Watts
Indicators:
Alarms (20 off)
Red LED’s Conditions: Alarm mode - Flashing Accept mode - Constant
Fault Alarm Amber LED
Power Green/Red LED Conditions: Mains On – Green State Mains Fail – Red State (battery back-up mode)
System Test - Stage 1 Alarm LED’s - ON Stage 2 Alarm relays - ON
Outputs - Alarm Relays (1) 3 sets S.P.C.O.(Rating 5A 230vAC) Latched until alarm reset (option - not resettable until signal has cleared – factory setting) Fault Relay - Set S.P.C.O Rating 5A 230v AC Mains Fail Relay - Set S.P.C.O Rating 5A 230v AC
Audible Alarm - Conditions: Gas / Fault Alarm (permanent mute option)
Signal Inputs - 20 way +24V DC (6 outputs) Field contacts, closing for alarm (20 inputs) Field contacts, closing for alarm Fault (1 input) Option at manufacture Alarm field contacts opening for +24V maintained alarm (loop failure monitored) connect jumper JP1-JP20 for unused inputs
Miscellaneous
Enclosure Wall mount - steel enclosure IP52 314W 264H 55D Cable entry Base or rear Field terminals 2.5mm Remote reset 2 wire - N/O Remote sounder 2 wire - 24v DC
Options
Channel Alarm Relays Add on board – 1 relay per channel

Brochure Downloads

Click to View PDF Document

GET IN TOUCH

Google Plus RSS Twitter

WANT TO BECOME A DISTRIBUTOR?